PID Controller SR80 Series ( SR82 / SR83 / SR84)
Shimaden SR80 series are suitable for applications with higher accuracy control is required.
Share:
Feature:
- High accuracy: ± (0.25% FS + 1 digit)
- Only SR83 (96 x 96) Large 20 mm bright display
Make reading from long distance and low light location easier. - 2-output heating and cooling control available for SR83 (96 x 96) and SR84 (48 x 96)
- Auto tuning function for both heating and cooling outputs in a high performance individual expert PID control
- Both RS232C/RS485 and CC-Link are communication interface ready. (CC-Link available only for SR83)
- Dust and splash proof front panel Equivalent to IP66
- A wide selection of additional functions (optional) is available to suit various needs.
Ordering Information
SR82
ITEMS | CODE | SPECIFICATIONS | ||||||||||||||
SERIES | SR82- | MPU-Based Auto-Tuning PID Digital Controller DIN H72 × W72 mm |
||||||||||||||
INPUT | 1 | Thermocouple | User-selectable inputs and ranges | |||||||||||||
2 | R.T.D. | User-selectable ranges | ||||||||||||||
3 | DC Voltage | User-selectable 0~10, 10~50, -10~10, 0~20, 0~50, 0~100mV DC linear inputs |
Programmable Range |
|||||||||||||
4 | DC Current | User-selectable 4~20, 0~20mA DC linear inputs |
||||||||||||||
5 | DC Voltage | User-selectable 0~1, 1~5, -1~1, 0~2, 0~5, 0~10V DC linear inputs |
||||||||||||||
CONTROL OUTPUT 1 | Y- | Contact | PB Cycle: 1~120 seconds, Contact Capacity: 240V AC 2.5A / resistive load, 1A / inductive load |
|||||||||||||
I- | Current | 4~20mA DC Load resistance: 600 Ω Max |
||||||||||||||
P- | SSR Voltage | PB Cycle 1~120 seconds, Output rating: 12V ±1.5V DC 30mA Max. |
||||||||||||||
V- | Voltage | 0~10V DC Maximum load current: 2mA Max. |
||||||||||||||
CONTROL OUTPUT 2 | N- | None | ||||||||||||||
POWER SUPPLY | 90- | 100~240V AC ±10% 50/60Hz | ||||||||||||||
10- | 24V AC ±10% 50/60Hz | |||||||||||||||
02- | 24V DC ±10% | |||||||||||||||
EVENT OUTPUT (2 points) [OPTION] | 0 | None | ||||||||||||||
1 | Contact output, Contact capacity: 240V AC 1A / resistive load | |||||||||||||||
2 | Contact output + Heater break alarm (with 30A CT) |
Selectable only for Y or P Control output | ||||||||||||||
3 | Contact output + Heater break alarm (with 50A CT) |
|||||||||||||||
REMOTE INPUT (Not selectable together with Heater break alarm function) [OPTION] |
00 | None | ||||||||||||||
14 | Current 4~20mA DC Receiving resistance: 250 Ω |
Non-Isolated input |
||||||||||||||
15 | Voltage 1~5V DC Input resistance: 500k Ω Min. |
|||||||||||||||
16 | Voltage 0~10V DC Input resistance: 500k Ω Min. |
|||||||||||||||
ANALOG OUTPUT (Not selectable together with Interface function) [OPTION] |
0 | None | ||||||||||||||
3 | Voltage 0~10mV DC, Output resistance: 10 Ω | |||||||||||||||
4 | Current 4~20mA DC, Load resistance: 300 Ω Max. | |||||||||||||||
6 | Voltage 0~10V DC, Load current: 2mA Max. | |||||||||||||||
INTERFACE FUNCTION (Not selectable together with Analog output function) [OPTION] |
0 | None | ||||||||||||||
5 | RS-485 | |||||||||||||||
7 | RS-232C | |||||||||||||||
EXTERNAL INPUT CONTROL SIGNAL / SET VALUE BIAS [OPTION] | 0 | None | ||||||||||||||
1 | Control input 2 points, Non-voltage contact, Open collector input (about 5V / 2mA impress) |
|||||||||||||||
REMARKS | 0 | Without | ||||||||||||||
9 | With (Please consult before ordering.) |
SR83
ITEMS | CODE | SPECIFICATIONS | ||||||||||||||
SERIES | SR83- | MPU-Based Auto-Tuning PID Digital Controller DIN H96 × W96 mm |
||||||||||||||
INPUT | 1 | Thermocouple | User-selectable inputs and ranges | |||||||||||||
2 | R.T.D. | User-selectable ranges | ||||||||||||||
3 | DC Voltage | User-selectable 0~10, 10~50, -10~10, 0~20, 0~50, 0~100mV DC linear inputs |
Programmable Range |
|||||||||||||
4 | DC Current | User-selectable 4~20, 0~20mA DC linear inputs |
||||||||||||||
5 | DC Voltage | User-selectable 0~1, 1~5, -1~1, 0~2, 0~5, 0~10V DC linear inputs |
||||||||||||||
CONTROL OUTPUT 1 | Y- | Contact | PB Cycle: 1~120 seconds, Contact Capacity: 240V AC 2.5A / resistive load, 1A / inductive load | |||||||||||||
I- | Current | 4~20mA DC Load resistance: 600 Ω Max. |
||||||||||||||
P- | SSR Voltage | PB Cycle 1~120 seconds, Output rating: 12V ±1.5V DC 30mA Max. | ||||||||||||||
V- | Voltage | 0~10V DC Maximum load current: 2mA Max. |
||||||||||||||
CONTROL OUTPUT 2 [OPTION] |
N- | None | ||||||||||||||
Y- | Contact | PB Cycle: 1~120 seconds, Contact Capacity: 240V AC 2.5A / resistive load, 1A / inductive load | ||||||||||||||
I- | Current | 4~20mA DC Load resistance: 600 Ω Max. |
||||||||||||||
P- | SSR Voltage | PB Cycle: 1~120 seconds, Output rating: 12V ±1.5V DC 30mA Max. | ||||||||||||||
V- | Voltage | 0~10V DC Maximum load current: 2mA Max. |
||||||||||||||
POWER SUPPLY | 90- | 100~240V AC ±10% 50/60Hz | ||||||||||||||
10- | 24V AC ±10% 50/60Hz | |||||||||||||||
02- | 24V DC ±10% | |||||||||||||||
EVENT OUTPUT (3 points) (2 points when 2 output option is added) [OPTION] | 0 | None | ||||||||||||||
1 | Contact output, Contact capacity: 240V AC 1A / resistive load | |||||||||||||||
2 | Contact output + Heater break alarm (with 30A CT) |
Selectable only for Y or P Control output | ||||||||||||||
3 | Contact output + Heater break alarm (with 50A CT) |
|||||||||||||||
REMOTE INPUT (Not selectable together with Heater break alarm function) [OPTION] |
00 | None | ||||||||||||||
14 | Current 4~20mA DC Receiving resistance: 250 Ω |
Non-Isolated input |
||||||||||||||
15 | Voltage 1~5V DC Input resistance: 500k Ω Min. |
|||||||||||||||
16 | Voltage 0~10V DC Input resistance: 500k Ω Min. |
|||||||||||||||
ANALOG OUTPUT (Not selectable together with CC-Link function) [OPTION] |
0 | None | ||||||||||||||
3 | Voltage 0~10mV DC, Output resistance: 10 Ω | |||||||||||||||
4 | Current 4~20mA DC, Load resistance: 300 Ω Max. | |||||||||||||||
6 | Voltage 0~10V DC, Load current: 2mA Max. | |||||||||||||||
INTERFACE FUNCTION (When CC-Link function is selected, simultaneous selection of Analog output is not possible) [OPTION] |
0 | None | ||||||||||||||
5 | RS-485 | |||||||||||||||
7 | RS-232C | |||||||||||||||
8 | CC-Link (Conforming with Mitsubishi Electric Company’s CCLink) (Not selectable together with Analog output function) |
|||||||||||||||
EXTERNAL INPUT CONTROL SIGNAL / SET VALUE BIAS [OPTION] | 0 | None | ||||||||||||||
1 | Control input 2 points, Non-voltage contact, Open collector input (about 5V / 2mA impress) |
|||||||||||||||
REMARKS | 0 | Without | ||||||||||||||
9 | With (Please consult before ordering.) |
SR84
ITEMS | CODE | SPECIFICATIONS | ||||||||||||||
SERIES | SR84- | MPU-Based Auto-Tuning PID Digital Controller DIN H96 × W96 mm |
||||||||||||||
INPUT | 1 | Thermocouple | User-selectable inputs and ranges | |||||||||||||
2 | R.T.D. | User-selectable ranges | ||||||||||||||
3 | DC Voltage | User-selectable 0~10, 10~50, -10~10, 0~20, 0~50, 0~100mV DC linear inputs |
Programmable Range |
|||||||||||||
4 | DC Current | User-selectable 4~20, 0~20mA DC linear inputs |
||||||||||||||
6 | DC Voltage | User-selectable 0~1, 1~5, -1~1, 0~2, 0~5, 0~10V DC linear inputs |
||||||||||||||
CONTROL OUTPUT 1 | Y- | Contact | PB Cycle: 1~120 seconds, Contact Capacity: 240V AC 2.5A / resistive load, 1A / inductive load | |||||||||||||
I- | Current | 4~20mA DC Load resistance: 600 Ω Max. |
||||||||||||||
P- | SSR Voltage | PB Cycle 1~120 seconds, Output rating: 12V ±1.5V DC 30mA Max. | ||||||||||||||
V- | Voltage | 0~10V DC Maximum load current: 2mA Max. |
||||||||||||||
CONTROL OUTPUT 2 [OPTION] |
N- | None | ||||||||||||||
Y- | Contact | PB Cycle: 1~120 seconds, Contact Capacity: 240V AC 2.5A / resistive load, 1A / inductive load | ||||||||||||||
I- | Current | 4~20mA DC Load resistance: 600 Ω Max. |
||||||||||||||
P- | SSR Voltage | PB Cycle: 1~120 seconds, Output rating: 12V ±1.5V DC 30mA Max. | ||||||||||||||
V- | Voltage | 0~10V DC Maximum load current: 2mA Max. |
||||||||||||||
POWER SUPPLY | 90- | 100~240V AC ±10% 50/60Hz | ||||||||||||||
10- | 24V AC ±10% 50/60Hz | |||||||||||||||
02- | 24V DC ±10% | |||||||||||||||
EVENT OUTPUT (3 points) (2 points when 2 output option is added) [OPTION] | 0 | None | ||||||||||||||
1 | Contact output, Contact capacity: 240V AC 1A / resistive load | |||||||||||||||
2 | Contact output + Heater break alarm (with 30A CT) |
Selectable only for Y or P Control output | ||||||||||||||
3 | Contact output + Heater break alarm (with 50A CT) |
|||||||||||||||
REMOTE INPUT (Not selectable together with Heater break alarm function) [OPTION] |
00 | None | ||||||||||||||
14 | Current 4~20mA DC Receiving resistance: 250 Ω |
Non-Isolated input |
||||||||||||||
15 | Voltage 1~5V DC Input resistance: 500k Ω Min. |
|||||||||||||||
16 | Voltage 0~10V DC Input resistance: 500k Ω Min. |
|||||||||||||||
ANALOG OUTPUT (Not selectable together with Interface function) [OPTION] |
0 | None | ||||||||||||||
3 | Voltage 0~10mV DC, Output resistance: 10 Ω | |||||||||||||||
4 | Current 4~20mA DC, Load resistance: 300 Ω Max. | |||||||||||||||
6 | Voltage 0~10V DC, Load current: 2mA Max. | |||||||||||||||
INTERFACE FUNCTION (Not selectable together with Analog output function) [OPTION] |
0 | None | ||||||||||||||
5 | RS-485 | |||||||||||||||
7 | RS-232C | |||||||||||||||
EXTERNAL INPUT CONTROL SIGNAL / SET VALUE BIAS [OPTION] | 0 | None | ||||||||||||||
1 | Control input 2 points, Non-voltage contact, Open collector input (about 5V / 2mA impress) |
|||||||||||||||
REMARKS | 0 | Without | ||||||||||||||
9 | With (Please consult before ordering.) |
Specification
SR82 (72 x 72) | Wide range of optional features |
Event output, Remote input, Analog output signal and Communication interface | |
SR83 (96 x 96) | Large 20 mm bright display (PV) |
Wide range of optional features | |
Event output, Remote input, Analog output signal and Communication interface | |
For example: Selectable One control output type or Two control output type. | |
SR84 (48 x 96) | Wide range of optional features |
Event output, Remote input, Analog output signal and Communication interface | |
For example: Selectable One control output type or Two control output type. | |
DISPLAY | |
LED display | Measured value (PV) display/ 7-segment red LED 4 digits Set value (SV) display/ 7-segment green LED 4 digits |
Display accuracy | ±(0.25% FS + 1 digit) |
Range in which display accuracy is maintained | 23˚C±5˚C |
Display resolution | Depends on measuring range (0.001, 0.01, 0.1, 1) |
Sampling cycle | 250 msec. (0.25 sec.) |
Action display/color | 11 types, LED lamp display |
Control output | (OUT1, 2)/green |
Event action | (EV1, 2, 3)/orange |
Auto tuning action | (AT)/green |
Manual control action | (MAN)/green |
Set value bias action | (SV2/SB)/green |
Remote action | (REM)/green |
Stand-by action | (STBY)/green |
Communication status | (COM/RUN)/green |
SETTING | |
Setting method | By front key switch operation |
Setting range | Same as measuring range (within setting limiter) |
Setting limiter | Higher and lower limits separate setting; free within measuring range (Lower limit < higher limit) |
Set value resolution | Depends on range and scaling (0.001, 0.01, 0.1, 1) |
Setting key type | 6 types – PARA (parameter selection), UP, DOWN, AT, ENT and DISP keys |
Ramp control upon reaching set value | Ascending/descending ramp control |
Ramp setting range | OFF, 1~9999 Units |
Ramp unit time | /sec, /min switching by front key operation and communication |
Ramp rate | x 1, x 0.1 switching by front key operation and communication |
INPUT | |
Thermocouple | B, R, S, K, E, J, T, N, PL II, |
WRe5-26, {L, U (DIN43710)} K, | |
AuFe-Cr Kelvin unit input | |
Allowable external resistance range | 100Ω maximum |
Input impedance | 500k Ω minimum |
Burnout function | Standard feature (up scale) |
Cold junction temperature compensation accuracy | ±2˚C (within a range from 5 to 45˚C) |
R.T.D. | Pt100/JPt100 |
Amperage | Approx. 0.25mA |
Allowable range of lead wire resistance | 5Ω maximum/wire |
Voltage (multiple input) | -10~10, 0~10, 0~20, 0~50, |
10~50, 0~100mV DC, or -1~1, | |
0~1, 0~2, 0~5, 1~5, 0~10V DC | |
Input impedance | 500k Ω minimum |
Current | 0~20mA, 4~20mA DC |
Receiving impedance | 250Ω |
Sampling cycle | 250 msec. (0.25 sec.) |
PV bias | -1999~1999 Units |
PV filter | OFF, 1~100 sec. |
Cold junction temperature compensation switching | INT (internal)/EXT (external) switching by front key operation |
Isolation | Insulated from various outputs [not insulated from system, DI (external switching input) and CT input] |
CONTROL (SR82: 1 output only) | |
Control system | One output operation: Expert PID control with auto tuning function |
RA (reverse action): Heating action | |
DA (direct action): Cooling action | |
Two output operation (option): Expert PID + PID (control outputs 1 and 2 individually in action) control with auto tuning function | |
RA (reverse action): Heating action (output 1 side) and cooling (output 2 side) | |
DA (direct action): 2-stage heating action (by both of control outputs 1 and 2) | |
PID (Control outputs 1 and 2 individually) Control output 1 | Proportional band (P); OFF, 0.1~999.9% (OFF=ON/OFF action) |
Integral time (I): OFF, 1~6000 sec. (OFF=with manual reset) | |
Derivative time (D): OFF, 0~3600 sec. | |
Manual reset: -50.0 to +50.0% (valid when I=OFF) | |
ON/OFF hysteresis: 1~1000 unit (valid during ON/OFF action) | |
Control output 2 (only when two output option is added) | Proportional band (P): OFF, 0.1~999.9% (OFF=ON/OFF action) |
Integral time (I): OFF, 1~6000 sec. | |
Derivative time (D): OFF, 0~3600 sec. | |
ON/OFF hysteresis: 1~1000 Units (valid during ON/OFF action) | |
Dead band: -1999~5000 Units Separate setting for SV2 is possible. | |
Setting range is the same as the one listed above. | |
Proportional cycle | (for contact and SSR drive voltage output) |
Control output 1 | 1~120 sec. |
Control output 2 | 1~120 sec. |
AT point setting | 0-5000 Units |
Control output characteristics | RA (reverse action)/DA (direct action) switchable by front key operation or DI (external switching input) through communication. |
Higher and lower limit output limiter (individually for control outputs 1 and 2) | Lower limit side: 0.0~99.9%, |
Higher limit side: 0.1~100.0% on condition that lower limit value < higher limit value. Separate setting for SB/SV2 is possible. Setting range is the same as the one listed above. | |
Control output at time of error (individually for control outputs 1 and 2) | 0.0~100.0% |
Control output type/rating (common to control outputs 1 and 2) | Contact (Y): 240V AC 2.5A/resistive load |
SSR drive voltage (P): 12V ±1.5V DC, load current 30mA maximum | |
Current (I): 4~20mA DC, load resistance 600Ω maximum | |
Voltage (V): 0~10V DC, load current 2mA maximum | |
Output resolution | |
Control output 1 | Approx. 0.0125% (1/8000) |
Control output 2 | Approx. 0.5% (1/200) |
Sampling cycle | 250 msec. (0.25 sec.) |
Manual control Manual switching | Front key operation or DI (external switching input) through communication |
Manual control output | 0.0-100.0% (out of output limiter range possible) |
Setting resolution | 0.10% |
Manual ↔ automatic control | Balanceless bumpless (within proportional band, though) |
Isolation | Insulated between control output and system and various inputs (not insulated between control output of current, voltage or SSR and analog output) |
EVENT OUTPUT (optional) | |
Number of event outputs | SR82 – 2 |
SR83 – 3 (2 when 2 output option is added) | |
SR84 – 3 (2 when communication option, analog output option and/or 2 output option are added) (In case of 2 event outputs, EV2 and EV3 are common output with OR.) | |
Event type | Selectable from 8 types (7 types when heater break alarm option is not added) |
A_Hi: Higher limit absolute value alarm | |
A_Lo: Lower limit absolute value alarm | |
D_Hi: Higher limit deviation value alarm | |
D_Lo: Lower limit deviation value alarm | |
D_i: Higher/lower limit deviation value alarm (within range) | |
D_o: Higher/lower limit deviation value alarm (out of range) | |
Sco: Scaleover (input trouble alarm) | |
Hb: Heater break alarm (selectable only when heater break alarm option is added) | |
Event setting range | Deviation value alarm |
Higher limit alarm: -1999~9999 Units | |
Lower limit alarm: -1999~9999 Units | |
Higher/lower limit alarm: 0~9999 Units | |
Absolute value alarm | |
Both higher and lower limits: Within measuring range | |
Event setting system | By front key operation |
Event action | ON/OFF action |
Event hysteresis | 1~1000 Units |
Stand-by/nonstand-by action | Selectable from 5 types |
Alarm action without stand-by | |
Alarm action with stand-by (When power is ON) | |
Alarm action with stand-by (When power is ON, when stand-by is switched to execution) | |
Alarm action with stand-by (When power is ON, when stand-by is switched to execution, including the time when SV is changed) | |
Control action | |
Event action delay | OFF, 1~9999 sec. |
Event output/rating | Contact 240V AC 1.0A (resistive load) |
Output updating cycle | 250 msec. (0.25 sec.) |
ANALOG OUTPUT (optional, not selectable together with communication type (1) and (2)) | |
The number of analog output | 1 |
Output signal | Selectable from 5 types (3 types for instrument with one output) |
PV: Measured value | |
SV: Set value | |
DEV: Deviation output | |
OUT 1: Control output 1 | |
OUT 2: Control output 2 (selectable only when 2 output option is added) | |
Output type/rating | 0~10mV DC/FS Output impedance: 10Ω 0~10V DC/FS Load current: 2mA maximum |
4~20mA DC/FS Load resistance: 300Ω maximum | |
Output scaling | PV/SV: Within measuring range (inverted scaling possible) OUT1/OUT2: 0.0-100.0% (inverted scaling possible) DEV: -100.0~100.0% (inverted scaling possible ) on condition that Ao_L ≠ Ao_H |
Output accuracy | ±0.3% FS (to displayed value) |
Output resolution | 0.01% FS (1/10000) |
Output updating cycle | 250 msec. (0.25 sec.) |
Isolation | Insulated from system and various inputs (not insulated from control outputs I, P and V) |
HEATER BREAK ALARM (optional, not selectable together with REM input) | |
Current capacity | 30A or 50A CT to be specified when order is placed. |
Alarm action | Heater amperage detected by external CT (CT attached). Alarm output ON upon detection of heater break while control output is ON. Alarm output ON upon detection of heater loop alarm while control output is OFF. |
Current setting range | 0.1~50.0A (Alarm action stops when OFF is set.) |
Setting resolution | 0.1A |
Current display | 0.0~55.0A |
Display accuracy | Approx. 3% FS (for 50Hz/60Hz sine wave) |
Minimum time for action confirmation | ON (OFF) time 250 msec. |
Alarm output/rating | Contact 240V AC 1.0A (resistive load) |
Alarm action display | ”Event” lamp lights during action. |
Alarm holding mode | Switchable between holding and not holding on the setting screen. |
Sampling time | 500 msec. (0.5 sec.) |
Isolation | Insulated between CT input and various outputs (not insulated from system and other inputs) |
REMOTE (optional, not selectable together with heater break alarm) | |
Remote setting | By external analog signal |
Switching to remote | By DI (external switching) input (valid only when DI option is added) Remote/local switching function by remote signal |
Remote switching point | OFF, 0.1~50.0% |
Remote switching hysteresis | 0.1~10.0% |
Remote scaling | Within measuring range (inverted scaling possible) |
Accuracy of setting | ±(0.25% SF + 1 digit) |
Setting signal | 0~10, 1~5V DC (Input impedance: 500k Ω min.) |
4~20mA DC (Receiving impedance: 250Ω) | |
Remote bias | -1999~1999 units |
Remote filter | OFF, 1~100 sec. |
Sampling cycle | 500 msec. (0.5 sec.) |
Isolation | Insulated between remote input and various outputs (not insulated from system and various inputs) |
COMMUNICATION (optional, not selectable together with analog output for SR82 and SR84) | |
Communication type (1) | RS-232C, RS-485 |
Communication system | RS-232C 3-line half duplex system |
RS-485 2-line half duplex multiple drop (bus) system | |
Synchronization system | Start-stop synchronization system |
Communication distance | RS-232C maximum 15 m |
RS-485 maximum 500 m (depending on conditions) | |
Communication speed | 1200, 2400, 4800, 9600, 19200 bps |
Data bit length | 7 bits, even parity, stop bit 1 |
7 bits, even parity, stop bit 2 | |
7 bits, no parity, stop bit 1 | |
7 bits, no parity, stop bit 2 | |
8 bits, even parity, stop bit 1 | |
8 bits, even parity, stop bit 2 | |
8 bits, no parity, stop bit 1 | |
8 bits, no parity, stop bit 2 | |
Communication address | 1~99 |
Communication memory mode | EEP/RAM/r_E |
Communication BCC | Add/Add two’s cmp/XOR/None |
Communication delay time | OFF, 1~100 |
Communication code | ASCII code |
Communication protocol | Shimaden standard protocol |
The number of instruments allowed to be connected | RS-232C 1 |
RS-485 32 maximum (depending on conditions; host included) | |
Isolation | Insulated between communication signal and various inputs/system/ various outputs |
Communication type (2) | Conforming with Mitsubishi Electric Company’s CC-Link (only for SR83, simultaneous selection of analog output is not possible) |
Transmission speed | 156K, 625K, 2.5M, 5M, 10Mbps |
Private station | 1 |
Communication method | Polling method |
Synchoronization method | Frame synchronous method |
Coding system | NRZI system |
Transmission line | Bus (RS-485) |
Transmission format | Conforming with HDLC |
DI (EXTERNAL SWITCHING) INPUT (optional) *DI stands for “Digital Input.” | |
Number of DI point | 2 |
DI input type | Selectable from 8 types (7 types if the remote option is not added.) |
NOP: No operation | |
STB: Execution/stand-by | |
SB/SV2: Set value bias/set value 2 | |
AT: Auto tuning | |
MAN: Manual | |
STP: Ramp temporary stop | |
DA: Direct action | |
REM: Remote (selectable only when remote option is added) | |
DI input rating | Nonvoltage contact, open collector input (about 5V/2mA impress) |
Isolation | Insulated between DI input and various outputs (not insulated from system and various inputs) |
SET VALUE 2 (SV2)/Set Value Bias (SB) (optional) (DI option is prerequisite.) | |
Action input | Nonvoltage contact by SB/SV2 selection through DI (external switching) input (in action during closed input) |
Selection of setting | Absolute value setting (SV2) |
Deviation value setting (SB) | |
Setting range | Absolute value setting: Within measuring range |
Deviation value setting: -1999~5000 Units SV2 allows PID and output limit to be set. | |
OTHERS | |
Data storage | By non-volatile memory (EEPROM) |
Ambient temperature/ humidity ranges for use | -10~+50˚C/below 90% RH (on condition that there is no dewcondensation) |
Temperature for storage | Between -20 and +65˚C |
Power supply | 100V-240V AC±10% (50/60 Hz), |
24V AC±10% (50/ 60Hz), | |
24V DC±10%. | |
(One of the above to be specified) | |
Power consumption | 12V A maximum |
Input noise removal ratio | Normal mode 60 dB minimum (50/60 Hz) |
Common mode 140 dB minimum (50/60 Hz) | |
Applicable standards | Safety: IEC1010-1 and EN61010-1 |
EMC: EN61326 | |
Insulation resistance | Between input/output terminals and power terminal 500V DC 20M Ω minimum Between input/output terminals and protective conductor terminal 500V DC 20M Ω minimum |
Dielectric strength | 1 minute at 2300V AC between input/output terminals and power terminal |
1 minute at 1500V AC between power terminal and protective conductor terminal | |
Protective structure | Only front panel has simple dustproof and drip-proof structure (equivalent to IP66) |
Material of case | PPO resin molding (equivalent to UL94V-1) |
External dimensions | SR82 H72 x W72 x D111 mm (Inside depth of panel: 100 mm) |
SR83 H96 x W96 x D111 mm (Inside depth of panel: 100 mm) |
|
SR84 H96 x W48 x D111 mm (Inside depth of panel: 100 mm) |
|
Mounting | Push-in panel (one-touch mount) |
Applicable panel thickness | 1.0~4.0 mm |
Panel cutout size | SR82: H68 x W68 mm |
SR83: H92 x W92 mm | |
SR84: H92 x W45 mm | |
Weight | SR82: 300g |
SR83: 420g | |
SR84: 280g |